![]() | PIZ Differential Pressure Transducer as a two-wire system |
In addition to differential pressure, the PIZ differential-pressure transducer also records positive and
negative overpressure. The central unit is a pressure cell with a
diaphragm spring made of beryllium bronze which, in accordance with the
pressure difference, is displaced between two chambers. The displacement
is measured, without making contact, via an inductive displacement
recorder. The device does not contain any components that can rub
against each other or parts subject to mechanical wear. The device is
best suited for use in air-conditioning and ventilation units, for
monitoring filling levels and for filter control.
Special features:
Measuring ranges:
from +/- 50 Pa to +/- 100 kPa
Linearity:
+/- 1%, optional +/- 0.5 +/- 0.2 %
Output signals:
0- 10V, 0- 20mA, 4- 20mA
Supply voltages:
24 VAC, 24 VDC, 230 VAC
Medium:
Air, all non aggressive gases
Time constants:
(optional) 1, 2, 5 s