PRODUCTS :: :: Pressure
P26 - Intelligent differential pressure transmitter with scaleable range

Freely scalable differential pressure transducer; Measurement ranges between ± 10 Pa and ± 100 kPa.

In addition to differential pressure data, the P 26 differential pressure transducer also records positive and negative overpressures. Measurement ranges between 100 Pa and 100 kPa are freely scalable from 10 to 100%; includes option of switching to other units, such as mmH2O. Two optional contact points allow the user to connect visual or audible alarms that would be triggered any time values fall above or below limits. The instrument can, if necessary, communicate with a master control unit via an RS 232 interface. The instrument can be mounted either on a wall or on top-hat rails. This pressure transducer is especially suited for monitoring pressure in clean rooms, for use in special mechanical engineering applications, or for monitoring a sterile environment such as a laboratory, pharmaceutical plant or operating room. room pressure

 

 

Measurement ranges:

100/ 250/ 500 Pa
1/ 2/ 4/ 10/ 20/40/ 100 kPa
free scalable from 10…100%
within a range

Margin of error
(0.3 Pa margin of error for reference)

0,3 Pa + 0,5% of end value for
measurement ranges <60 Pa
0,5% end value for measurement
ranges  > 60 Pa

Medium:

Air, all non- aggressive gases

Time constants:

25 ms … 60s (adjustable)

Output:

0…10V
0…20mA
4…20mA

Power supply:

24 VDC
24 VAC
230/ 115 VAC

 

DATASHEET» P26.en.pdf (214kB)
HANDBOOK» P26.en.pdf (615kB)