![]() | ACCUBALANCE® Capture Hood 8375 |
The TSI Model 8375 AccuBalance Modular Air Balancing Tool is deal for HVAC testing and balancing and also for industrial hygiene applications. The heart of the Model 8375 is a revolutionary micro manometer that easily detachs from the base for use with a wide variety of probes to measure diffuser flow rate, point velocity, average velocity, pressure differential, temperature and humidity. Simplify your business with this economical and comprehensive measurement solution.
Air Velocity:
Range: 25 to 8,000 ft/min (0.13 to 41m/s) Pitot Probe; 25 to 5,000 ft/min (0.13 to 25m/s) Air Flow Probe; 25 to 2,500 ft/min (0.13 to 13m/s) Velocity Matrix
Accuracy: 3% of reading, +/-7 ft/min (0.04m/s) All Probes
Volume:
Range: 25 to 2,500 ft³ CFM (42 to 4,250m³/h) Capture Hood
Accuracy: +/- 3% of reading, +/- 7ft³/min at >50ft/min (+/-11.9m³/h at >0.25m/s)
Resolution: 1 ft³/min (1 m³/h)
Differential Pressure:
Range: +/-15 in. wc83735 Pa), 150 in. wc maximum safe operating pressure
Accuracy: 2% of reading, +/-0.001 in. wc (0.025 m wc) from 0.050 to 15 in. wc
Resolution: 0.00001 in. wc (0.00025 mm wc)
Absolute Pressure:
Range: 15 to 40 in. Hg(356 to 1016 mm Hg)
Accuracy: 2% of reading
Resolution: 0.01 in. Hg (1 mm Hg)
Temperature Probe:
Range: -40 to 250°F (-40 to 121°C) probe dependent
Accuracy: 0.5°F (0.3°C) from 32 to 160°F (0 to 71°C), typically 2.0°F (1.2°C) from -40 to 32°F (-40 to 0°C) and from 160 to 250°F 871 to 121°C)
Resolution: 0.1°F (0.1°C)
Relative Humidity Probe:
Range: 0 to 95% RH
Accuracy: 3% RH
Resolution: 0.1% RH
Statistics: min, max, average up to 1,00 readings for each measured parameters
Averaging Capability: up to 1,000 values each of measured parameters
Sampling Interval: Continuous or user selectable (10 to 600s)
Response Time: 2 to 8 s
| DATASHEET | » |